WA024 LOW TEMP HEATING PART LOAD (Antifreeze Required)

Entering Fluid Temp. (°F)
Entering Air Temp. (°F)
Total Capacity (MBtuH)
Power Input (kW)
Heat of Absortion (MBtuH)
COP
25°F 60°F 15,096 1.099 11,344 4.03
30°F   15,809 1.108 12,026 4.18
40°F   17,235 1.125 13,394 4.49
25°F 70°F 14,330 1.095 9,964 3.84
30°F   14,945 1.128 11,075 3.88
40°F   16,293 1.146 12,381 4.17
25°F 80°F 13,363 1.144 9,398 3.42
30°F   13,931 1.153 9,956 3.54
40°F   15,186 1.171 11,188 3.80