WA036 COOLING PERFORMANCE PART LOAD

Entering Fluid Temp. (°F)
Entering Air Temp. (°F)
Total Capacity (MBtuH)
Sensible Capacity (MBtuH)
Sensible to Total Ratio
Power Input (kW)
Heat of Rejection (MBtuH)
EER
50°F 70°F DB 61°F WB 27,121 17,627 0.65 0.959 33,039 28.3
60°F 25,735 16,865 0.66 1.054 31,351 24.4
70°F 24,349 16,153 0.66 1.150 29,662 21.2
85°F 22,271 15,165 0.68 1.294 27,130 17.2
100°F 20,192 14,228 0.70 1.437 24,598 14.0
50°F 75°F DB 63°F WB 29,054 21,012 0.72 0.964 35,393 30.1
60°F 27,571 20,104 0.73 1.061 33,586 26.0
70°F 26,087 19,261 0.74 1.157 31,779 22.6
85°F 23,861 18,078 0.76 1.301 29,068 18.3
100°F 21,636 16,959 0.78 1.446 26,357 15.0
50°F 80°F DB 67°F WB 31,881 23,176 0.73 0.972 38,837 32.8
60°F 30,255 22,181 0.73 1.069 36,856 28.3
70°F 28,628 21,252 0.74 1.166 34,875 24.6
85°F 26,189 19,951 0.76 1.312 31,903 20.0
100°F 23,750 18,717 0.79 1.452 28,932 16.4
50°F 85°F DB 71°F WB 34,708 25,370 0.73 0.979 42,281 35.4
60°F 32,939 24,280 0.74 1.077 40,126 30.6
70°F 31,170 23,263 0.75 1.175 37,971 26.5
85°F 28,517 21,840 0.77 1.322 34,739 21.6
100°F 25,863 20,489 0.79 1.469 31,506 17.6