WA036 COOLING PERFORMANCE FULL LOAD

Entering Fluid Temp. (°F)
Entering Air Temp. (°F)
Total Capacity (Btu/H)
Sensible Capacity (MBtuH)
Sensible to Total Ratio
Power Input (kW)
Heat of Rejection (MBtuH)
EER
50°F 70°F DB 61°F WB 37,357 24,270 0.65 1.808 43,530 20.7
60°F 35,448 23,220 0.66 1.988 42,235 17.8
70°F 33,539 22,240 0.66 2.169 40,944 15.5
85°F 30,676 20,880 0.68 2.440 39,006 12.6
100°F 27,813 19,590 0.70 2.710 37,065 10.3
50°F 75°F DB 63°F WB 40,019 28,930 0.72 1.818 46,226 22.0
60°F 37,976 27,680 0.73 2.000 44,804 19.0
70°F 35,932 26,520 0.74 2.181 43,378 16.5
85°F 32,867 24,890 0.76 2.453 41,242 13.4
100°F 29,802 23,350 0.78 2.726 39,109 10.9
50°F 80°F DB 67°F WB 43,913 31,910 0.73 1.832 50,167 24.0
60°F 41,673 30,540 0.73 2.015 48,552 20.7
70°F 39,433 29,260 0.74 2.198 46,937 17.9
85°F 36,073 27,470 0.76 2.473 44,516 14.6
100°F 32,713 25,770 0.79 2.738 40,680 11.9
50°F 85°F DB 71°F WB 47,807 34,930 0.73 1.846 54,109 25.9
60°F 45,370 33,430 0.74 2.031 52,304 22.3
70°F 42,934 32,030 0.75 2.215 50,496 19.4
85°F 39,279 30,070 0.77 2.492 47,787 15.8
100°F 35,624 28,210 0.79 2.769 45,077 12.9