WA036 HEATING PERFORMANCE PART LOAD

Entering Fluid Temp. (°F)
Entering Air Temp. (°F)
Total Capacity (MBtuH)
Power Input (kW)
Heat of Absortion (MBtuH)
COP
50°F 60°F 24,685 1.525 19,479 4.74
60°F 26,349 1.530 21,349 5.05
70°F 28,460 1.536 23,216 5.43
80°F 30,347 1.542 25,083 5.77
50°F 70°F 23,337 1.553 18,035 4.40
60°F 25,121 1.558 19,802 4.73
70°F 26,904 1.564 21,565 5.04
80°F 28,687 1.570 23,327 5.35
50°F 80°F 21,754 1.587 16,336 4.02
60°F 23,415 1.592 17,980 4.31
70°F 25,076 1.598 19,620 4.60
80°F 26,737 1.604 21,261 4.89