WA048 COOLING PERFORMANCE PART LOAD

Entering Fluid Temp. (°F)
Entering Air Temp. (°F)
Total Capacity (MBtuH)
Sensible Capacity (MBtuH)
Sensible to Total Ratio
Power Input (kW)
Heat of Rejection (MBtuH)
EER
50°F 70°F DB 61°F WB 33,661 21,397 0.64 1.366 41,006 24.6
60°F 32,257 20,678 0.64 1.493 39,295 21.6
70°F 30,853 20,024 0.65 1.619 37,585 19.1
85°F 28,747 19,145 0.67 1.809 35,019 15.9
100°F 26,641 18,361 0.69 1.998 32,454 13.3
50°F 75°F DB 63°F WB 36,061 25,515 0.71 1.374 43,930 26.2
60°F 34,558 24,658 0.71 1.501 42,099 23.0
70°F 33,056 23,873 0.72 1.628 40,268 20.3
85°F 30,801 22,835 0.74 1.819 37,522 16.9
100°F 28,546 21,891 0.77 2.010 34,775 14.2
50°F 80°F DB 67°F WB 39,572 28,144 0.71 1.385 48,207 28.6
60°F 37,925 27,200 0.72 1.513 46,200 25.1
70°F 36,277 26,343 0.73 1.641 44,192 22.1
85°F 33,805 25,195 0.75 1.834 41,182 18.4
100°F 31,334 24,157 0.77 2.026 38,171 15.5
50°F 85°F DB 71°F WB 43,083 30,802 0.71 1.395 52,484 30.9
60°F 41,291 29,771 0.72 1.525 50,300 27.1
70°F 39,499 28,834 0.73 1.654 48,117 23.9
85°F 36,810 27,578 0.75 1.848 44,842 19.9
100°F 34,121 26,445 0.78 2.042 41,567 16.7