WA048 COOLING PERFORMANCE FULL LOAD

Entering Fluid Temp. (°F)

Entering Air Temp. (°F)

Total Capacity (Btu/H)

Sensible Capacity (MBtuH)

Sensible to Total Ratio

Power Input (kW)

Heat of Rejection (MBtuH)

EER

50°F 70°F DB 61°F WB 46,365 29,460 0.64 2.576 55,159 18.0
60°F 44,431 28,470 0.64 2.815 54,041 15.8
70°F 42,497 27,570 0.65 3.053 52,920 13.9
85°F 39,596 26,360 0.67 3.410 51,238 11.6
100°F 36,695 25,280 0.69 3.767 49,556 9.7
50°F 75°F DB 63°F WB 49,671 35,130 0.71 2.591 58,517 19.2
60°F 47,601 33,950 0.71 2.830 57,263 16.8
70°F 45,531 32,870 0.72 3.070 56,012 14.8
85°F 42,426 31,440 0.74 3.430 54,136 12.4
100°F 39,320 30,140 0.77 3.789 52,256 10.4
50°F 80°F DB 67°F WB 54,507 38,750 0.71 2.611 63,421 20.9
60°F 52,238 37,450 0.72 2.853 61,978 18.3
70°F 49,968 36,270 0.73 3.094 60,531 16.1
85°F 46,564 34,690 0.74 3.457 58,366 13.5
100°F 43,160 33,260 0.77 3.819 56,198 11.3
50°F 85°F DB 71°F WB 59,343 42,410 0.71 2.631 68,325 22.6
60°F 56,874 40,990 0.72 2.875 66,689 19.8
70°F 54,406 39,700 0.73 3.119 65,054 17.4
85°F 50,702 37,970 0.75 3.484 62,596 14.6
100°F 46,999 36,410 0.77 3.850 60,143 12.2