WA060 COOLING PERFORMANCE PART LOAD

Entering Fluid Temp. (°F)
Entering Air Temp. (°F)
Total Capacity (MBtuH)
Sensible Capacity (MBtuH)
Sensible to Total Ratio
Power Input (kW)
Heat of Rejection (MBtuH)
EER
50°F 70°F DB 61°F WB 43,066 27,251 0.63 1.690 52,463 25.5
60°F 41,207 26,285 0.64 1.844 50,198 22.4
70°F 39,340 25,413 0.65 1.997 47,925 19.7
85°F 36,546 24,229 0.66 2.227 44,520 16.4
100°F 33,752 23,147 0.69 2.457 41,117 13.7
50°F 75°F DB 63°F WB 46,135 32,480 0.70 1.700 56,202 27.1
60°F 44,142 31,340 0.71 1.854 53,773 23.8
70°F 42,148 30,301 0.72 2.009 51,345 21.0
85°F 39,157 28,885 0.74 2.240 47,701 17.5
100°F 36,166 27,599 0.76 2.471 44,058 14.6
50°F 80°F DB 67°F WB 51,672 37,332 0.72 1.749 62,947 29.5
60°F 49,441 36,017 0.73 1.907 60,229 25.9
70°F 47,210 34,826 0.74 2.066 57,512 22.9
85°F 43,864 33,206 0.76 2.304 53,435 19.0
100°F 40,518 31,732 0.78 2.542 49,359 15.9
50°F 85°F DB 71°F WB 56,256 40,862 0.73 1.762 68,531 31.9
60°F 53,829 39,424 0.73 1.922 65,574 28.0
70°F 51,402 38,116 0.74 2.082 62,618 24.7
85°F 47,762 36,344 0.76 2.322 58,184 20.6
100°F 44,122 34,739 0.79 2.562 53,749 17.2