WA060 COOLING PERFORMANCE FULL LOAD

Entering Fluid Temp. (°F)
Entering Air Temp. (°F)
Total Capacity (Btu/H)
Sensible Capacity (MBtuH)
Sensible to Total Ratio
Power Input (kW)
Heat of Rejection (MBtuH)
EER
50°F 70°F DB 61°F WB 59,319 37,520 0.63 3.187 70,199 18.6
60°F 56,759 36,190 0.64 3.476 68,620 16.3
70°F 54,188 34,990 0.65 3.765 67,042 14.4
85°F 50,339 33,360 0.66 4.199 64,670 12.0
100°F 46,491 31,870 0.69 4.632 62,305 10.0
50°F 75°F DB 63°F WB 63,547 44,720 0.70 3.205 74,489 19.8
60°F 60,801 43,150 0.71 3.496 72,736 17.4
70°F 58,055 41,720 0.72 3.787 70,984 15.3
85°F 53,935 39,770 0.74 4.223 68,352 12.8
100°F 49,816 38,000 0.76 4.659 65,722 10.7
50°F 80°F DB 67°F WB 71,174 51,400 0.72 3.297 82,430 21.6
60°F 68,101 49,590 0.73 3.596 80,378 18.9
70°F 65,028 47,950 0.74 3.895 78,326 16.7
85°F 60,419 45,720 0.76 4.344 75,249 13.9
100°F 55,810 43,690 0.78 4.793 72,173 11.6
50°F 85°F DB 71°F WB 77,487 56,260 0.73 3.322 88,828 23.3
60°F 74,144 54,280 0.73 3.624 86,516 20.5
70°F 70,802 52,480 0.74 3.926 84,205 18.0
85°F 65,788 50,040 0.76 4.378 80,734 15.0
100°F 60,774 47,830 0.79 4.831 77,267 12.6