WA072 COOLING PERFORMANCE PART LOAD

Entering Fluid Temp. (°F)
Entering Air Temp. (°F)
Total Capacity (MBtuH)
Sensible Capacity (MBtuH)
Sensible to Total Ratio
Power Input (kW)
Heat of Rejection (MBtuH)
EER
50°F 70°F DB 61°F WB 50,535 32,823 0.65 1.841 56,820 27.5
60°F 48,828 31,987 0.66 2.164 56,220 22.6
70°F 47,126 31,250 0.66 2.486 55,615 19.0
85°F 44,570 30,332 0.68 2.970 54,713 15.0
100°F 42,813 30,163 0.70 3.454 52,155 12.4
50°F 75°F DB 63°F WB 54,138 39,131 0.72 1.851 60,293 29.2
60°F 52,309 38,131 0.73 2.176 59,597 24.0
70°F 50,487 37,259 0.74 2.500 58,898 20.2
85°F 47,750 36,161 0.76 2.987 57,851 16.0
100°F 45,869 35,959 0.78 3.474 55,878 13.2
50°F 80°F DB 67°F WB 59,406 43,170 0.73 1.866 65,370 31.8
60°F 57,402 42,068 0.73 2.193 64,533 26.2
70°F 55,404 41,107 0.74 2.520 63,693 22.0
85°F 52,402 39,896 0.76 3.011 62,440 17.4
100°F 50,341 39,678 0.79 3.501 61,325 14.4
50°F 85°F DB 71°F WB 64,677 47,246 0.73 1.880 70,448 34.4
60°F 62,494 46,042 0.74 2.210 69,469 28.3
70°F 60,320 44,992 0.75 2.540 68,489 23.8
85°F 57,055 43,667 0.77 3.034 67,029 18.8
100°F 53,770 43,425 0.81 3.529 65,503 15.2