WA072 COOLING PERFORMANCE FULL LOAD

Entering Fluid Temp. (°F)
Entering Air Temp. (°F)
Total Capacity (Btu/H)
Sensible Capacity (MBtuH)
Sensible to Total Ratio
Power Input (kW)
Heat of Rejection (MBtuH)
EER
50°F 70°F DB 61°F WB 66,810 43,400 0.65 3.578 79,026 18.7
60°F 65,243 42,740 0.66 3.944 78,708 16.5
70°F 63,675 42,230 0.66 4.309 78,386 14.8
85°F 61,323 41,740 0.68 4.858 77,908 12.6
100°F 58,971 41,530 0.70 5.406 77,427 10.9
50°F 75°F DB 63°F WB 71,573 51,740 0.72 3.598 83,857 19.9
60°F 69,895 50,950 0.73 3.966 83,435 17.6
70°F 68,217 50,350 0.74 4.334 83,013 15.7
85°F 65,699 49,760 0.76 4.885 82,376 13.4
100°F 63,181 49,510 0.78 5.437 81,743 11.6
50°F 80°F DB 67°F WB 78,538 57,080 0.73 3.626 90,918 21.7
60°F 76,700 56,210 0.73 3.997 90,346 19.2
70°F 74,860 55,550 0.74 4.368 89,772 17.1
85°F 72,100 54,900 0.76 4.924 88,911 14.6
100°F 69,340 54,630 0.79 5.480 88,049 12.7
50°F 85°F DB 71°F WB 85,506 62,470 0.73 3.654 97,981 23.4
60°F 83,504 61,520 0.74 4.028 97,256 20.7
70°F 81,503 60,800 0.75 4.402 96,531 18.5
85°F 78,501 60,090 0.77 4.963 95,445 15.8
100°F 75,499 59,790 0.79 5.524 94,358 13.7