WA024 COOLING PERFORMANCE (FULL LOAD)

Entering Fluid Temp. (°F)
Entering Air Temp. (°F)
Total Capacity (Btu/H)
Sensible Capacity (MBtuH)
Sensible to Total Ratio
Power Input (kW)
Heat of Rejection (MBtuH)
EER
50°F 70°F DB 61°F WB 25,539 16,590 0.65 1.12 29,349 22.9
60°F   24,618 16,130 0.66 1.27 28,937 19.5
70°F   23,698 16,115 0.68 1.41 28,525 16.8
85°F   22,318 15,190 0.68 1.64 27,907 13.6
100°F   20,937 14,237 0.68 1.86 27,287 11.3
50°F 75°F DB 63°F WB 27,358 19,780 0.72 1.12 31,189 24.4
60°F   26,373 19,230 0.73 1.27 30,716 20.7
70°F   25,388 18,740 0.74 1.42 30,243 17.9
85°F   23,910 18,110 0.76 1.65 29,523 14.5
100°F   22,432 17,580 0.78 1.87 28,816 12.0
50°F 80°F DB 67°F WB 30,019 21,820 0.73 1.13 33,880 26.5
60°F   28,940 21,210 0.73 1.28 33,317 22.6
70°F   27,860 20,670 0.74 1.43 32,752 19.4
85°F   26,240 19,980 0.76 1.66 31,904 15.8
100°F   24,620 19,400 0.79 1.89 31,055 13.1
50°F 85°F DB 71°F WB 32,681 23,880 0.73 1.14 36,573 28.7
60°F   31,506 23,210 0.74 1.29 35,917 24.4
70°F   30,331 22,630 0.75 1.44 35,261 21.0
85°F   28,569 21,870 0.77 1.67 34,277 17.1
100°F   26,807 21,230 0.79 1.90 33,294 14.1