WW024 CHILLER PERFORMANCE PART LOAD

Leaving Load Fluid (°F)
Entering Source Fluid (°F)
Total Capacity
Total Capacity (MBtuH)
Power Input (kW)
EER
Heat Rejection (MBtuH)
(Tons)
40°F 75° 1.3 15,311 0.89 17.2 18,146
80° 1.2 14,953 0.97 1.1 18,064
85° 1.2 14,576 1.05 13.9 17,765
90° 1.2 14,160 1.13 12.5 17,611
95° 1.1 13,748 1.22 11.3 17,479
42°F 75° 1.3 15,859 0.89 17.8 18,540
80° 1.3 15,467 0.97 15.9 18,387
85° 1.3 15,080 1.05 14.4 18,248
90° 1.2 14,652 1.13 13.0 18,085
95° 1.2 14,229 1.22 11.7 17,942
44°F 75° 1.4 16,401 0.89 18.4 19,054
80° 1.3 15,993 0.97 16.5 18,891
85° 1.3 15,595 1.05 14.9 18,743
90° 1.3 15,157 1.13 13.4 18,569
95° 1.2 14,700 1.22 12.0 18,395
45°F 75° 1.4 16,656 0.89 18.7 19,304
80° 1.4 16,272 0.97 16.8 19,159
85° 1.3 15,869 1.05 15.1 19,005
90° 1.3 15,424 1.13 13.6 18,826
95° 1.2 14,962 1.22 12.3 18,646
46°F 75° 1.4 16,943 0.89 19.0 19,580
80° 1.4 16,554 0.97 17.1 19,430
85° 1.3 16,123 1.05 15.4 19,315
90° 1.3 15,695 1.13 13.9 19,085
95° 1.3 15,226 1.22 12.5 18,899
48°F 75° 1.5 17,527 0.89 19.7 20,141
80° 1.4 17,104 0.97 17.6 19,957
85° 1.4 16,685 1.05 15.9 19,789
90° 1.4 16,222 1.13 14.4 19,592
95° 1.3 15,741 1.22 12.9 19,395
50°F 75° 1.5 18,099 0.89 20.3 20,691
80° 1.5 17,690 0.97 18.2 20,520
85° 1.4 17,235 1.05 16.4 20,317
90° 1.4 16,761 1.13 14.8 20,141
95° 1.4 16,268 1.22 13.3 19,901