WW024 HEATING PERFORMANCE FULL LOAD

Leaving Load Fluid (°F)
Entering Source Fluid (°F)
Total Capacity (MBtuH)
Power Input (Kw)
COP
Heat Rejection (MBtuH)
100°F 35° 24,366 1.96 3.6 17,683
40° 25,857 1.95 3.9 19,205
50° 29,107 1.93 4.4 29,107
60° 32,739 1.90 5.0 26,250
70° 36,779 1.88 5.7 30,367
110°F 35° 24,224 2.21 3.2 16,686
40° 25,652 2.20 3.4 18,140
50° 28,764 2.18 3.9 21,318
60° 32,249 2.16 4.4 24,890
70° 36,137 2.13 5.0 28,870
120°F 35° 24,128 2.50 2.8 15,608
40° 25,482 2.49 3.0 16,972
50° 28,443 2.48 3.4 19,997
60° 31,763 2.45 3.8 23,396
70° 35,478 2.42 4.3 27,207
125°F 35° 24,111 2.66 2.7 15,030
40° 25,426 2.66 2.8 16,363
50° 28,302 2.64 3.1 19,285
60° 31,536 2.62 3.5 22,601
70° 35,160 2.59 4.0 26,328