WW036 CHILLER PERFORMANCE FULL LOAD

Leaving Load Fluid (°F)
Entering Source Fluid (°F)
Total Capacity
Total Capacity (MBtuH)
Power Input (kW)
EER
Heat Rejection (MBtuH)
(Tons)
40°F 75° 2.1 24,752 1.63 15.2 30,301
80° 2.0 24,135 1.73 14.0 30,037
85° 2.0 23,534 1.84 12.8 29,809
90° 1.9 22,872 1.96 11.7 29,545
95° 1.8 22,184 2.08 10.7 29,285
42°F 75° 2.1 25,598 1.61 15.9 31,146
80° 2.1 25,001 1.73 14.5 30,903
85° 2.0 24,345 1.84 13.2 30,620
90° 2.0 23,664 1.96 12.1 30,338
95° 1.9 22,959 2.08 11.0 30,060
44°F 75° 2.1 25,598 1.63 15.7 31,146
80° 2.1 25,001 1.73 14.5 30,903
85° 2.0 24,345 1.84 13.2 30,620
90° 2.0 24,476 1.96 12.5 31,151
95° 2.0 23,751 2.08 11.4 30,853
45°F 75° 2.2 26,904 1.63 16.5 32,451
80° 2.2 26,282 1.73 15.2 32,184
85° 2.1 25,597 1.84 13.9 31,874
90° 2.1 24,889 1.96 12.7 31,564
95° 2.0 24,155 2.08 11.6 31,257
46°F 75° 2.3 27,350 1.63 16.8 32,896
80° 2.2 26,719 1.73 15.4 32,621
85° 2.2 26,025 1.84 14.1 32,302
90° 2.1 25,307 1.96 12.9 31,983
95° 2.1 25,022 2.12 11.8 32,243
48°F 75° 2.4 28,950 1.65 17.5 34,594
80° 2.3 27,607 1.73 16.0 33,510
85° 2.2 26,894 1.84 14.6 33,172
90° 2.2 26,157 1.96 13.4 32,834
95° 2.1 25,431 2.08 12.2 32,532
50°F 75° 2.4 29,226 1.63 18.0 34,772
80° 2.4 28,516 1.73 16.5 34,419
85° 2.3 27,824 1.84 15.1 34,104
90° 2.3 27,066 1.96 13.8 33,745
95° 2.2 26,281 2.08 12.6 33,387