WW036 HEATING PERFORMANCE PART LOAD

Leaving Load Fluid (°F)
Entering Source Fluid (°F)
Total Capacity (MBtuH)
Power Input (Kw)
COP
Heat Rejection (MBtuH)
100°F 35° 18,680 1.44 3.8 13,831
40° 19,849 1.43 4.1 15,039
50° 22,406 1.41 4.6 17,684
60° 25,278 1.40 5.3 20,647
70° 28,486 1.39 6.0 23,949
110°F 35° 18,523 1.63 3.3 12,971
40° 19,636 1.62 3.5 14,130
50° 22,076 1.61 4.0 16,667
60° 24,815 1.59 4.6 19,501
70° 27,886 1.57 5.2 22,674
120°F 35° 18,397 1.86 2.9 12,025
40° 19,451 1.85 3.1 13,132
50° 21,759 1.83 3.5 15,548
60° 24,360 1.81 3.9 18,259
70° 27,278 1.79 4.5 21,286
125°F 35° 18,350 1.99 2.7 11,512
40° 19,369 1.98 2.9 12,582
50° 21,609 1.96 3.2 14,939
60° 24,136 1.93 3.7 17,587
70° 26,976 1.91 4.1 20,546